Withdrawal and injection at mixed sites explained

Infographic of the net flow at the electricity meter of a mixed site: consumption, solar panels and battery, with the withdrawal and injection cases

Withdrawal and injection explained for mixed sites combining consumption, solar panels and a battery

A consuming site equipped with solar panels and a battery does not just consume or produce: in reality, it withdraws or it injects.

The difference matters: what the power grid sees is neither the site’s gross consumption nor the panels’ gross generation, but the net flow measured at the electricity meter.

  • When the site withdraws, electricity flows from the grid to the site.
  • When the site injects, electricity flows from the site to the grid.

At any given moment, this net flow depends on four elements:

consumption + battery charging − battery discharging − solar generation

  • If the result is positive, the site is withdrawing.
  • If it is negative, the site is injecting.

For example, if a site consumes 5 kW, its battery charges at 3 kW and its panels produce 6 kW, the meter will see a net withdrawal of 2 kW.

It is this net power, whether withdrawn or injected, that must be controlled and monetised on flexibility mechanisms.